How to read a generator nameplate: kW, kVA, voltage, phase and Hz

Decode a generator nameplate: kW vs kVA, power factor, voltage, phase, Hz, prime vs standby ratings, and the engine and emissions labels.

Updated November 9, 2026 · 7 min read

Key takeaways

  • kW is real power. kVA is apparent power. kW equals kVA times the power factor.
  • Most three-phase commercial sets are rated at a 0.8 power factor, so 100 kVA is about 80 kW.
  • Voltage, phase and frequency must match your equipment. Phase and voltage are often not interchangeable.
  • Prime and standby ratings differ. A standby rating is only for limited emergency hours.

Where to find the nameplates

Many units have more than one plate: one on the generator end (alternator), one on the engine, and sometimes a control panel or enclosure tag. If the unit is in an enclosure, check inside the door or on the frame. Photograph every plate. If you can't find a plate, look at the engine or alternator for a model number, then search the manufacturer's site or ask a dealer.

What each line means

FieldWhat it tells youWhy it matters
Make, model, serialIdentifies the exact unitNeeded for parts, manuals and value
kWReal power the generator can deliverThe number most buyers compare
kVAApparent powerSets the size of the alternator and current limit
Power factor (PF)Ratio of kW to kVA, often 0.8 or 1.0kW = kVA × PF
Voltage and phaseFor example 120/240 V single-phase or 277/480 V three-phaseMust match your panel and loads
AmpsCurrent at the rated voltageSizing breakers and wiring
Hz and RPM60 Hz is usually 1,800 RPM and 50 Hz is usually 1,500 RPMA 50 Hz unit won't match 60 Hz equipment
Rating classStandby, prime or continuousSets how many hours and what duty it can run
Date or yearWhen it was builtAffects parts, value and emissions rules

kW vs kVA, in plain English

kW is the real power that does work. kVA is the total power the alternator can supply, including power that doesn't do work. The link is power factor: kW = kVA × PF. Most three-phase commercial and industrial sets use PF 0.8, so a 125 kVA set is about 100 kW. Many home single-phase units are rated at a PF of 1.0, so kVA and kW are the same.

Voltage and phase

  • Single-phase 120/240 V is typical for homes and small shops.
  • Three-phase (such as 120/208 V, 277/480 V or 346/600 V) is common in commercial buildings and industry.
  • Many three-phase sets can be reconnected for other voltages, but check the reconnection chart and have a qualified technician do it.
  • A three-phase unit run as single-phase usually delivers less power, often around two thirds of its kVA.

If you're not sure what you have, an electrician can read your panel and meter label. This also matters for the sizing of your generator.

Standby, prime and continuous ratings

RatingMeant forTypical use
Emergency standby (ESP)Backup during a utility outageHospitals, homes, buildings with limited annual hours
Prime (PRP)Variable load, unlimited hours, in place of the utilityRemote sites, rentals, events
Continuous (COP)Constant load, unlimited hoursBase load plants
Defined in ISO 8528-1. Makers set the exact limits, so read the spec sheet.

A standby rating is usually higher than the prime rating for the same hardware, but it only allows limited hours per year. Running a standby-rated unit as prime can shorten its life and affect warranty.

The engine and emissions label

The engine usually has its own plate with the engine model, serial and rated horsepower, plus an emissions label showing the standard it meets, such as EPA Tier 3 or Tier 4 Final for larger diesels. Some buyers and projects require a specific tier, so photograph it.

Know what it's worth

Enter the model or specs, hours, age and condition for a fair market value estimate.

Price a generator

Frequently asked questions

What is the difference between kW and kVA on a generator?

kW is real power. kVA is apparent power. kW equals kVA times the power factor. At a 0.8 power factor, 100 kVA is 80 kW.

What power factor do generators use?

Most three-phase commercial sets are rated at 0.8. Many single-phase units are rated at 1.0. Check the nameplate.

Is a standby rating the same as prime?

No. Standby is for emergencies with limited hours, and prime is for variable loads with unlimited hours. Don't run a standby-rated unit as prime.

Can a 60 Hz generator run 50 Hz equipment?

Usually not directly. Motors and some devices depend on frequency. Some units can be set up for either frequency, but that needs the maker or a qualified technician.