How to read a generator nameplate: kW, kVA, voltage, phase and Hz
Decode a generator nameplate: kW vs kVA, power factor, voltage, phase, Hz, prime vs standby ratings, and the engine and emissions labels.
Updated November 9, 2026 · 7 min read
Key takeaways
- kW is real power. kVA is apparent power. kW equals kVA times the power factor.
- Most three-phase commercial sets are rated at a 0.8 power factor, so 100 kVA is about 80 kW.
- Voltage, phase and frequency must match your equipment. Phase and voltage are often not interchangeable.
- Prime and standby ratings differ. A standby rating is only for limited emergency hours.
Where to find the nameplates
Many units have more than one plate: one on the generator end (alternator), one on the engine, and sometimes a control panel or enclosure tag. If the unit is in an enclosure, check inside the door or on the frame. Photograph every plate. If you can't find a plate, look at the engine or alternator for a model number, then search the manufacturer's site or ask a dealer.
What each line means
| Field | What it tells you | Why it matters |
|---|---|---|
| Make, model, serial | Identifies the exact unit | Needed for parts, manuals and value |
| kW | Real power the generator can deliver | The number most buyers compare |
| kVA | Apparent power | Sets the size of the alternator and current limit |
| Power factor (PF) | Ratio of kW to kVA, often 0.8 or 1.0 | kW = kVA × PF |
| Voltage and phase | For example 120/240 V single-phase or 277/480 V three-phase | Must match your panel and loads |
| Amps | Current at the rated voltage | Sizing breakers and wiring |
| Hz and RPM | 60 Hz is usually 1,800 RPM and 50 Hz is usually 1,500 RPM | A 50 Hz unit won't match 60 Hz equipment |
| Rating class | Standby, prime or continuous | Sets how many hours and what duty it can run |
| Date or year | When it was built | Affects parts, value and emissions rules |
kW vs kVA, in plain English
kW is the real power that does work. kVA is the total power the alternator can supply, including power that doesn't do work. The link is power factor: kW = kVA × PF. Most three-phase commercial and industrial sets use PF 0.8, so a 125 kVA set is about 100 kW. Many home single-phase units are rated at a PF of 1.0, so kVA and kW are the same.
Voltage and phase
- Single-phase 120/240 V is typical for homes and small shops.
- Three-phase (such as 120/208 V, 277/480 V or 346/600 V) is common in commercial buildings and industry.
- Many three-phase sets can be reconnected for other voltages, but check the reconnection chart and have a qualified technician do it.
- A three-phase unit run as single-phase usually delivers less power, often around two thirds of its kVA.
If you're not sure what you have, an electrician can read your panel and meter label. This also matters for the sizing of your generator.
Standby, prime and continuous ratings
| Rating | Meant for | Typical use |
|---|---|---|
| Emergency standby (ESP) | Backup during a utility outage | Hospitals, homes, buildings with limited annual hours |
| Prime (PRP) | Variable load, unlimited hours, in place of the utility | Remote sites, rentals, events |
| Continuous (COP) | Constant load, unlimited hours | Base load plants |
A standby rating is usually higher than the prime rating for the same hardware, but it only allows limited hours per year. Running a standby-rated unit as prime can shorten its life and affect warranty.
The engine and emissions label
The engine usually has its own plate with the engine model, serial and rated horsepower, plus an emissions label showing the standard it meets, such as EPA Tier 3 or Tier 4 Final for larger diesels. Some buyers and projects require a specific tier, so photograph it.
Know what it's worth
Enter the model or specs, hours, age and condition for a fair market value estimate.
Frequently asked questions
What is the difference between kW and kVA on a generator?
kW is real power. kVA is apparent power. kW equals kVA times the power factor. At a 0.8 power factor, 100 kVA is 80 kW.
What power factor do generators use?
Most three-phase commercial sets are rated at 0.8. Many single-phase units are rated at 1.0. Check the nameplate.
Is a standby rating the same as prime?
No. Standby is for emergencies with limited hours, and prime is for variable loads with unlimited hours. Don't run a standby-rated unit as prime.
Can a 60 Hz generator run 50 Hz equipment?
Usually not directly. Motors and some devices depend on frequency. Some units can be set up for either frequency, but that needs the maker or a qualified technician.
Sources
- Cummins: Understanding ISO 8528 generator set ratings
- World Standards: Three-phase electric power by country
GenTrak is a research and reference tool. We are not electricians, contractors or dealers. Before you buy, install, connect or remove any generator, talk to a licensed electrician or other certified professional.