Load sizing worksheet

List the loads, set the headroom and get a minimum generator size. It adds all running watts, then the single largest motor starting surge on top.

Add a typical load

Result

2.6 kW minimum

Running load 0.7 kW, plus the largest starting surge 1.4 kW, gives a peak of 2.1 kW. With 25% headroom, look for a unit rated at least 2.6 kW (3.3 kVA at 0.8 power factor).

Running current at 240 V single-phase is about 2.9 A.

The preset figures are typical planning values, not measurements. Use nameplate full-load and locked-rotor amps, the motor type and any soft starter or inverter drive for the real job. Single-phase math only. For three-phase loads, size from the nameplate data and the manufacturer's sizing tool.