50 kW generators: compare prices, specs and fuel costs across brands

In GenTrak's catalog, a 50 kW generator costs about $25,000 new and $4,750 to $18,000 used, depending on hours. We list models at this size from Cummins, Caterpillar, Generac, HiPower, Kohler, Blue Star, MTU, and Taylor Power Systems.

Catalog data compiled November 8, 2026. Prices are before installation and delivery, and accurate to about 20 to 30 percent on industrial units.

Models
23
Brands
8
Typical new price
$25,000
Typical used price
$4,750 to $18,000

Running and moving a 50 kW generator

Fuel burn at 75% load
2.9 gal of diesel per hour
Freight, about 500 miles
$1,100 to $2,250
Shipping weight about 3,020 lb, including unloading at delivery
Median price per kW
$500

Fuel burn is a typical engineering value for this rating. Freight is a ballpark, not a carrier quote.

Fifty kilowatts is a workhorse size for small commercial buildings, farms, restaurants and shops, and it is also common as a rental unit. We list 23 models from 8 brands, with a typical new price around $25,000.

Watch for: your largest motor. A single big pump or compressor can need far more than its running watts to start, and that surge is often what sets the real size you need.

How much does a 50 kW generator cost?

New and zero-hour prices at this size, split by fuel and by brand. 22 models of 23 have a price.

FuelModelsRangeMedian
Diesel11$24,000 to $26,400$24,000
Gas11$23,881 to $27,500$25,000
BrandModelsRangeMedian
Cummins8$23,881 to $25,000$24,000
Caterpillar3$24,000 to $25,000$24,000
Generac3$24,000 to $25,000$25,000
HiPower2$25,000$25,000
Kohler1$25,000$25,000
Blue Star3$25,200 to $26,200$25,200
MTU2$26,400 to $27,500$26,950
Taylor Power Systems1$44,000$44,000

What is a used 50 kW generator worth?

Typical fair market value for a maintained unit that runs and has service records. Each row is the median of the 22 models at this size, and the range is the lowest and highest model.

Hours on meterTypical value% of new
1–250 hrs$18,00072%
251–500 hrs$16,80067%
501–1,000 hrs$15,05060%
1,001–2,000 hrs$12,25049%
2,001–4,000 hrs$9,80039%
4,001–7,500 hrs$7,70031%
7,501–10,000 hrs$6,10024%
10,000+ hrs$4,75019%

Value depends on the depreciation class of each model. How we price, or run your own unit through Price a Gen.

Which generators are rated 50 kW?

Models for permanent installation, plus mobile and portable units below. Sorted by price, lowest first.

7 brands. Tap a brand to see its models.

Mobile, towable and portable at 50 kW

  • New$44,000

    GenTrak estimate

    Used$27,500

    Used price range, 501 to 1,000 hrs
    $20,600$34,400
    Rating
    50 kW (prime, per Taylor)
    Fuel
    Diesel (Tier 4F)
    Voltage
    Configurable: 120/240 1Ø; 120/208, 120/240, 277/480, 347/600 3Ø

Estimated value is GenTrak's estimate of fair market value where a list price is not published. Voltage and phase are as listed by the manufacturer, and many models are configurable, so confirm on the spec sheet before you buy.

What can a 50 kW generator run?

Plan on about 40 kW of steady load. At this size we mostly see whole-home backup on large properties and light commercial sites.

  • A large home or two: about 7 average whole-home backup loads at 6 kW each.
  • Around 5,000 sq. ft. of retail or office space at a typical 8 watts per square foot.
  • Central air: roughly 11 3-ton units running at once, with the starting surge staggered.

Electrical and fuel at 50 kW

Full-load current
75 A at 480 V three-phase and 208 A at 240 V single-phase
Diesel
2.1 gal/hr at half load, 3.7 gal/hr full
Natural gas
303 ft³/hr at half load, 550 ft³/hr full

Typical values, not manufacturer ratings. Cost to run turns the burn rate into dollars per hour.

Diesel vs. gas at 50 kW

Both fuels are available at this rating in our catalog, so here is how they compare.

DieselGas
Models1111
Median new price$24,000$25,000
Price per kW$480$500
Fuel at half load2.1 gal/hr303 ft³/hr
Fuel at full load3.7 gal/hr550 ft³/hr

Gas here means natural gas. Diesel is stored on site and suits long outages. Gas avoids a fuel tank but depends on the utility line or a propane supply.

Buying checklist for a 50 kW generator

Voltage and phase

Confirm 120/208, 120/240, 277/480 or 347/600 V, and single or three-phase, before you compare prices. Many models are configurable.

Enclosure

Open, weather-protected or sound-attenuated. Sound-attenuated costs more and adds size, and some sites need it for noise limits.

Emissions and air permit

Rules differ for emergency standby and for prime or peak-shaving use, and vary by state. Ask your state air office before you buy.

Transfer switch (ATS)

Size the ATS to the load and the service, not just the generator. Plan for it in the budget.

Freight and install

Delivery and a pad, plus a licensed electrician for hardwired setups.

Fuel supply

Decide between on-site diesel storage and a gas line before you pick a model.

Get a delivered number with the freight estimator. Hardwired installs need a licensed electrician, so see licensed electricians.

State rules

Permits, electrician licensing, air quality and fuel storage are set by your state and often your county. Look up the regulator for your state before you install a 50 kW generator.

State generator regulators →

Where to buy a 50 kW generator

Official dealer locators

Ask a dealer about lead times, parts and who handles warranty service.

Previous and next size

Size 97 of 302. See every size or browse all 50 to 100 kW generators.

Common questions

How much does a 50 kW generator cost?

In our catalog, a 50 kW generator runs from $23,881 to $27,500 new, with a median of $25,000 (about $500 per kW). Used units typically sell for $4,750 to $18,000 used. Installation, freight, fuel supply and permits are usually extra, and industrial estimates are accurate to about 20 to 30 percent.

What can a 50 kW generator run?

Plan on about 40 kW of steady load. At this size we mostly see whole-home backup on large properties and light commercial sites. A large home or two: about 7 average whole-home backup loads at 6 kW each. Around 5,000 sq. ft. of retail or office space at a typical 8 watts per square foot. Central air: roughly 11 3-ton units running at once, with the starting surge staggered.

How much fuel does a 50 kW generator use?

Diesel: about 2.1 gal per hour at half load and 3.7 gal per hour at full load. Natural gas: about 303 ft³ per hour at half load and 550 ft³ per hour at full load. These are typical engineering values, so check the spec sheet of the exact unit. The Fuel Hub turns them into dollars per hour.

What size breaker and wire does a 50 kW generator need?

Full-load current is about 75 A at 480 V three-phase and 208 A at 240 V single-phase. A licensed electrician sizes the breaker, conductors and transfer equipment from the nameplate and local code, so use these numbers only for planning.

Is a 50 kW generator better as diesel or gas?

We list 11 diesel models and 11 gas models at 50 kW. Diesel median is $24,000 and gas is $25,000. Diesel stores on site and holds up under long runs; gas avoids on-site fuel storage but depends on the utility or a propane tank. The comparison table above shows both side by side.