Decommissioning guide

A general order of work for taking a generator out of service safely and legally. Rules differ by state, fuel and city, so use this as a checklist and confirm each step with the office for your area.

  1. 1.Plan and notify

    Confirm who owns the unit and the fuel system. Check the permits on file, and whether the air agency, the fire marshal, the utility or the insurer need notice before work starts.

  2. 2.Shut down and lock out

    Turn off the unit and the automatic start. Open and lock out the generator breaker, the transfer switch and the battery charger. Disconnect the battery and prove all sources are dead before you touch conductors.

  3. 3.Disconnect the electrical side

    Remove or cap the generator feed and the transfer equipment, or return the service to utility only. Label what stays energized, and leave the panel safe and labeled.

  4. 4.Isolate and handle the fuel

    Shut the fuel supply at the source. Propane tanks and natural gas lines should be isolated and removed or capped by a licensed gas or propane company. Gasoline and diesel need safe draining, transport and storage.

  5. 5.Close or remove fuel tanks

    Underground diesel or gasoline tanks usually need a closure or removal permit and a licensed contractor. Aboveground tanks may need a permit or notice. Your state's fire and fuel office, shown below, can tell you the rule.

  6. 6.Handle fluids, batteries and waste

    Drain and dispose of oil, coolant and fuel through licensed channels. Recycle batteries. Keep records of what was removed and where it went.

  7. 7.Notify and record

    If the engine held an air permit or registration, tell the air agency it is out of service. Tell the utility, the insurer and the local building department as required, and keep the closure paperwork.

  8. 8.Remove, sell or store the unit

    Check the data plate and hours before you sell. Our sell page can estimate used value and find buyers and brokers.

Who to call about fuel and tanks in your state

Pick a state to see the office that handles fire code, propane or fuel tank removal and closure.

See who licenses electricians, who issues permits, and who to call about air rules and fuel.

State-level offices only, compiled November 8, 2026 from each agency's own website. Phone numbers and agency structures change. Cities and counties add their own permits, noise, setback and HOA rules, so confirm with your local building department before you start.

For the electrical and air offices in your state, see state regulations. For safety basics, read the CO, clearance and backfeed reminders.

Sell the unit and check its used value →

More for electricians

GenTrak is a research tool, not a dealer or broker. We don't sell generators, take a cut or vouch for any seller. Follow your local code and authority having jurisdiction for every installation.